Method of Statement for Fire Fighting Works (Part-2)
Method of Statement for Fire Fighting Works (Part-2) 8 Votes (5) Vertical risers Vertical risers shall be parallel to walls and column lines and shall be straight and in plumb. Risers passing from floor to floor shall be supported at each floor by MS angle with clamp as per specification of pipe support. The space in the floor cut outs around the pipes work may be closed using cement concrete (1:2:4 mix) or steel sheet, from the fire safety considerations, taking care to see that a small annular space is left around the pipes to prevent transmission of vibration to the structure. Riser shall have suitable supports at the lowest point. (6) Sprinkler Heads & Accessories Installation of sprinkler heads will be done after pipe work flushing is completed. Apply the PTFE tape only to the male portion of the sprinkler and install the upright sprinkler head using the wrench provided by the manufacturer, and in such a way that the arms are parallel t...